COLUMBUS -- November 25, 2026 -- Data center teams that tighten cold plate flatness below 0.025 mm may add machining cost without a measurable cooling gain, according to new guidance from MES, Inc. The company says a 0.015 mm callout can move the contact face from precision CNC machining to grinding or dedicated fly cutting. That cuts the allowed deviation by 40% from 0.025 mm, by our calculation.

A 0.025 mm tolerance equals 1 part in 2,800 on a 70 mm die

The guidance ties the problem to larger AI processor packages. Across a 30 mm die, 0.025 mm works out to 1 part in 1,200. Across a 70 mm die, the same tolerance is 1 part in 2,800. The 70 mm span is about 2.3 times the 30 mm span, and MES says residual stress relaxation, heat from the cut and fixture distortion act over more than twice the distance.

MES identifies 0.025 mm across the die contact footprint as a good working specification for most direct-to-chip applications. The thermal model should set the final number. "If it doesn't show a measurable benefit, a tighter tolerance can add cost without improving cooling," said CEO Hiten Shah.

A dished cold plate can add TIM thicker than the typical layer

Thermal interface material (TIM) typically forms a layer 25 to 75 microns thick and conducts a few W/m·K, against about 388 W/m·K for copper. A plate dished 0.040 mm can add up to 40 microns of TIM locally. By our calculation, that equals roughly 53% of a 75-micron layer and 160% of a 25-micron layer.

A flat but rough face can leave microscopic voids. MES describes 0.4 to 0.8 µm Ra as a useful working range for many contact faces, depending on the TIM and contact pressure. It suggests specifying both Ra and Rz on critical die interfaces.

Engineering Manager Brad Layne said a cold plate can pass a flatness check and still add thermal resistance if no surface finish was specified. MES recommends measuring flatness across the die footprint, where it affects heat transfer.

As-brazed plates run 0.100 to 0.250 mm out of flat

A vacuum braze cycle can relieve residual stress and change the shape of the base, MES says. As-brazed flatness therefore commonly runs 0.100 to 0.250 mm, or four to ten times the 0.025 mm working specification. The guidance recommends machining the mounting face after brazing and calling out that sequence as a process note on the drawing.

MES did not state in the release how much more grinding or fly cutting costs than precision CNC machining.

MES supplies copper and aluminum cold plates through a manufacturing network spanning eight countries. Its engineers review drawings before tooling begins, and parts are verified by CMM at the source. The full guidance compares the flatness and surface finish that five machining processes can typically hold and includes a contact face specification checklist.